Wuhan Global Metal Engineering Co., Ltd

Wuhan Global Metal Engineering Co., Ltd The pioneer manufacturer of heaters & sensors

Manufacturer from China
Verified Supplier
10 Years
Home / Products / Hot Runner Temperature Controller /

Innovative Industrial TC RTD pid temperature controller with digital display

Contact Now
Wuhan Global Metal Engineering Co., Ltd
Visit Website
City:wuhan
Province/State:hubei
Country/Region:china
Contact Person:MrFrank
Contact Now

Innovative Industrial TC RTD pid temperature controller with digital display

Ask Latest Price
Video Channel
Brand Name :GME
Model Number :REX-C100 Temperature Controller
Certification :ISO9001 CE
Place of Origin :China
MOQ :10pcs
Payment Terms :L/C, D/A, D/P, T/T, Western Union, MoneyGram
Supply Ability :100000pcs/month
Delivery Time :7-15days
Packaging Details :Standard Export Packing
Usage :Industrial
Product name :C100 Intelligent PID temperature controller
Input signal :Thermocouple,RTD
Power Supply :AC110-240V,220V 50/60 Hz
more
Contact Now

Add to Cart

Find Similar Videos
View Product Description

Innovative Industrial TC RTD pid temperature controller with digital display

General Description


REX series PID Temperature Controller is the new product developed by
our company. It adopts special microcomputer adjusting meter that
employs switching power and surface mount technology (SMT), therefore,
the controller is quite smart and reliable. Its special functions like auto
diagnosing, auto setting and intelligent control. It can be used widely in the
display and control of the parameter of the temperature, pressure, flow, and
liquid level.

Specitications

Input Specifications Thermocouple: K, J, S,R Thermal Resistance: Pt100,RTD
Output Signal optional output
Measurement Precision 1.0 class (±1.0%F±1),0.5 class(±0.5%F+1)
Regulating Methods Intelligent PID control, according to the value of P,I,D parameters,
we can get P(P=0 is on-off control),PI,PD,PID regulating mode
Alarm function (optional function) Upper limit, lower limit, deviation value, absolute value
Contact Capacity(Resistive Load): AC250V 2A
Power supply AC85-AC265V 50/60 Hz
Power Consumption ≤10VA
Working Conditions Temperature :-10-50℃
Humidity: ≤85%RH non-corrosive environment

1,Input:
Thermocouple(TC),Resistance Temperature Detect(RTD)
Standard Current and voltage signals.
2,Display:
Process Value(PV), Setting Value(SV):-1999~+1999
Output ( OUT1 ,OUT2 ) Alarm ( ALM1 ,ALM2 ) Auto setting(AT)
Display: LED
3,Control Way
(1).PID Control(including ON/OFF, position PID and continuous PID)
(2).Auto Setting Control
4.Accuracy
Measurement Accuracy:±0.5%FS
Compensation error of cold terminal: ±2℃(amend within 0~50℃ by soft)
Resolution:14bit. Samplingperiod:0.5Sec.
5.Setting Range:
Setting Value(SV): same range with PV
Proportional Band(P):0~full range(ON/OFF Control when set to 0)
IntegrationTime(I):0~3600Sec(no integral action when set to 0)
Derivative Time(D):0~3600Sec(no derivative action when set to 0)
Proportional Period:1~100Sec
On-off control output hysteretic loop width:1~100℃(or other PV units)
6.Control Output
(1)Currency output: DC 0~10Ma,4~20mA(RL<500Ω)
(2)Voltage output: DC 0-5V,1-5V(RL>10K)
(3)Relay output: Contact capacity:250V AC 3A(resistive load)
(4)Voltage Impulse output:0-12V(applicable for solid state relay SSR)
(5)Silicon Controlled Rectifier(SCR) output: zero-cross triggering or
phase-shift triggering(resistive load)
(6)Alarming function output: 2 groups output at most,12 modes
Output Contact Capacity:250V AC 3A
7.Other Parameters
(1)Insulation resistance:>50MΩ(500V DC)
(2)Insulation strength:1500V AC/min
(3)Power consumption:<10V
(4)Service environment:0~50℃,30~85RH,no corrosive gas
(5)Weight:abt.0.5Kg(C900 type)

5.First Control Output(OUT1) (Heating side)
M: Relay contact output 8:Current output(DC 4~20mA)
V: Voltage impulse output T: Hydration driving output
6.Second Control Output(OUT2) (Cooling side)
Null: when control operation is F or D
M: Relay Contact output
8: Current output( DC 4~20mA)
V: Voltage impulse output
T: Hydration driving output
7.First Alarm(ALM1) 8.Second Alarm(ALM2)
N: no alarm A: Upper-Limit bias alarm
B: Lower-Limit bias alarm C: Upper/Lower Limit bias alarm
D: Alarm in area
E: Standby upper-limit bias alarm attached
F: Standby lower-limit bias alarm attached
G: Standby upper/lower limit bias alarm attached
H: Upper-Limit input value alarm
J: Lower-limit input value alarm
K: Standby upper-limit input value alarm attached
L: Standby lower-limit input value alarm attached

Applications

Innovative Industrial TC RTD pid temperature controller with digital display

Inquiry Cart 0